Home / Inspections / Fire Alarms
Inspection guide · UK housing

Fire Detection & Alarm Service

Fire detection and alarm systems in communal areas need a weekly call-point test, plus planned servicing that checks detectors, panels, batteries and cause-and-effect. The inspection produces a service certificate and defect list.

Quick answer

For communal fire alarm systems, BS 5839-1 recommends a weekly user test, operating a different manual call point each week, and servicing by a competent person at intervals not exceeding six months, with a logbook. Alarms inside individual homes follow BS 5839-6, which grades systems A to F and sets coverage categories LD1 to LD3.

Reviewed 15 October 2026. Confirm against the official guidance below before relying on it.

BS 5839-1 system categories

CategoryProtects
L1All areas of the building
L2Escape routes and defined high-risk rooms
L3Escape routes and the rooms opening onto them
L4Escape routes only
L5Areas defined by the fire risk assessment
P1 / P2Property protection: all areas, or defined areas

Why it matters

An alarm system that fails to sound is the single most dangerous failure in a residential fire. Weekly test logs and six-monthly service certificates are the evidence regulators, insurers and the FRA all depend on.

How Kaarr runs it

  • Weekly test rotas with call-point rotation tracked per building
  • Six-monthly service visits scheduled with certificate capture
  • Defects from the service raised as prioritised remedial tickets
  • Grade and category of each system recorded per building (BS 5839)

Communal systems and dwelling alarms

A communal system in a block has a control panel, call points and a logbook, and the routine is weekly test, periodic service and a record of every fault and false alarm. Dwelling alarms are different: BS 5839-6 grades the equipment (A to F, by whether there is a control panel, mains power and so on) and the coverage (LD1 to LD3).

The landlord's legal minimum for rented homes in England is set by the Smoke and Carbon Monoxide Alarm (England) Regulations 2015 as amended: a smoke alarm on every storey used as living accommodation, a carbon monoxide alarm in any room with a fixed combustion appliance (other than a gas cooker), and a check that each works at the start of the tenancy.

What the logbook records

Weekly tests, service visits, faults, false alarms, and any changes to the system. A system that tests on time but has no record of faults being cleared will not stand up to scrutiny.

The regulation

Fire Safety Order 2005 · BS 5839-1 & BS 5839-6

The maintenance duty flows from the Regulatory Reform (Fire Safety) Order 2005; BS 5839-1 (communal/commercial) and BS 5839-6 (dwellings) define system grades, categories and the testing regime. Smoke and carbon monoxide alarm requirements in individual homes are set by the Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022.

Regulatory frameworks differ across the UK — see the city pages below for Scotland, Wales and Northern Ireland specifics.

Common questions

How often should a fire alarm be tested?

BS 5839-1 recommends a weekly user test of one manual call point (a different one each week) and servicing by a competent person at intervals not exceeding six months.

What is a fire alarm logbook?

The record kept with the system: tests, service visits, faults, false alarms, and any changes. It is the evidence that the system was maintained.

What grade of fire alarm does a landlord need?

The legal minimum for rented homes in England is a smoke alarm on each storey and a carbon monoxide alarm where there is a fixed combustion appliance. For blocks, the fire risk assessment decides the communal system; BS 5839-6 sets grades A to F and LD1 to LD3 for dwellings.

What is the difference between BS 5839-1 and BS 5839-6?

BS 5839-1 is the code of practice for fire detection and alarm systems in non-domestic premises, including the communal areas of blocks. BS 5839-6 covers systems in domestic premises.

Do we really have to test the alarm every week?

For communal systems, yes — BS 5839-1 expects a weekly test from a different call point each time, logged. It takes minutes and it's the first record a fire officer asks for.

What's the difference between BS 5839-1 and 5839-6?

Part 1 covers communal and commercial systems; Part 6 covers detection inside dwellings, with grades from mains-interlinked alarms to full panel systems.

Who can service a fire alarm system?

A competent servicing organisation — typically third-party certificated (e.g. BAFE SP203). Kaarr stores the certificates and chases the next visit.

Frequency
Weekly test + 6-monthly service

BS 5839-1 expects a weekly user test of communal systems and periodic servicing by a competent firm — normally every six months. Domestic (in-flat) systems follow BS 5839-6. Kaarr runs both schedules.

Fire Alarms by city

Local guides for housing providers across the UK

We also support providers in Liverpool, Sheffield, Bristol, Newcastle upon Tyne, Nottingham, Leicester, Coventry, Bradford, Southampton, Portsmouth, Sunderland, Edinburgh, Swansea, and anywhere else across the UK.

See your whole portfolio's compliance in one calm view

A 30-minute demo with your own inspection types and stock profile. No obligation, no setup required.