There is no fixed legal interval for a fire risk assessment. What the Fire Safety Order requires, what triggers an early review and how door checks fit in.
There is no fixed legal interval for a fire risk assessment. The Fire Safety Order requires the assessment to be reviewed regularly, and in particular when there is reason to suspect it is no longer valid or when something significant has changed.
An annual review is the common default for residential blocks, and it is a sensible baseline. It is a convention, though, not wording in the law, and several events should trigger a review long before the year is up.
In England and Wales the duty sits in the Regulatory Reform (Fire Safety) Order 2005. Article 9 requires the responsible person to make a suitable and sufficient assessment of the risks to people from fire, and then to keep it current. The review wording is the important part: the assessment must be reviewed regularly so as to keep it up to date, and particularly if there is reason to suspect it is no longer valid or there has been a significant change in the matters it relates to.
Article 9 also requires the findings and the measures taken to be recorded, and the record to be made as soon as practicable after the assessment is made or reviewed. An assessment that was reviewed but not written down has not met the duty.
The Order names two triggers: reason to suspect the assessment is no longer valid, and a significant change. In a residential block those translate into everyday events, and each of them should lead to a dated review entry rather than waiting for the annual visit:
Buildings change faster than a multi-year cycle can track. Doors get replaced, wedged or damaged, penetrations are made for new cabling, and residents change. A yearly review is frequent enough to catch drift and infrequent enough to be practical across a large portfolio, which is why it became the default in the housing sector.
Where the building or the residents carry more risk, a shorter interval is easier to defend than a longer one. Taller blocks, buildings with a stay-put strategy, buildings with known compartmentation problems and buildings with a high proportion of vulnerable residents all justify closer attention.
The assessment review is only one of the recurring items. In England, the Fire Safety (England) Regulations 2022 add fixed intervals for fire door checks in taller residential buildings. These are separate duties and they are not satisfied by the FRA review.
| Check | Interval | Applies to | Source |
|---|---|---|---|
| Flat entrance doors | At least every 12 months (best endeavours) | Buildings above 11 metres with two or more sets of domestic premises | Fire Safety (England) Regulations 2022, reg 10 |
| Communal fire doors | At least every 3 months | The same buildings | Fire Safety (England) Regulations 2022, reg 10 |
| Self-closing devices on those doors | Checked as part of each door check | The same buildings | Fire Safety (England) Regulations 2022, reg 10 |
The regulations also require the responsible person to keep a record of the steps taken on flat entrance doors, including attempts to gain access. Access refusals are routine, so the evidence of reasonable attempts matters as much as the completed checks.
Alarm and emergency lighting testing sit on their own schedules too. Emergency lighting is covered in our guide to the monthly and annual tests.
In purpose-built blocks of flats, assessments are commonly described as Type 1 to Type 4. The classification comes from the Local Government Association's guide Fire safety in purpose-built blocks of flats and describes how far the assessment goes, not how often it is done.
| Type | Where it looks | Invasive? |
|---|---|---|
| Type 1 | Common parts only | No: visual inspection, no opening up |
| Type 2 | Common parts only | Yes: sampling to check concealed fire stopping and compartmentation |
| Type 3 | Common parts and inside flats | No: visual inspection |
| Type 4 | Common parts and inside flats | Yes: sampling inside flats too |
A Type 1 assessment is the usual baseline for the yearly review. The higher types are used when there is a reason to look behind the finishes, such as a concern about compartmentation, works history or construction. Because the invasive types usually need access to homes, they are scheduled as projects, not as part of the yearly review.
In England, a building that is at least 18 metres high or has at least seven storeys, and contains at least two residential units, is a higher-risk building under section 65 of the Building Safety Act 2022. These buildings sit in a more intensive regime administered by the Building Safety Regulator, with additional duties for the accountable person. If one of your blocks meets that test, treat the FRA review as one part of a wider set of obligations, and follow the regulator's guidance directly.
The Fire Safety Order applies in Wales as it does in England. In Scotland, the Fire (Scotland) Act 2005 and the Fire Safety (Scotland) Regulations 2006 cover non-domestic premises, and a stair or passage used in common by more than one dwelling is treated as domestic premises, so most blocks of flats fall outside them. The Scottish Government publishes practical fire safety guidance for existing high-rise domestic buildings. In Northern Ireland the equivalent duty comes from the Fire and Rescue Services (NI) Order 2006 and the Fire Safety Regulations (NI) 2010.
The practical test is whether someone who has never seen your building could read the file and understand what was found, what was done, and when.
No fixed interval is stated. The Fire Safety Order requires the assessment to be reviewed regularly, and particularly if there is reason to suspect it is no longer valid or there has been a significant change. Annual review is the common practice for residential blocks.
Building works, a change in use or in the residents, new or altered fire safety systems, and findings from routine checks that suggest the assessment is out of date. The responsible person judges this and should record the review.
They are separate duties. In England, for buildings above 11 metres with two or more sets of domestic premises, flat entrance doors must be checked at least every 12 months and communal fire doors at least every 3 months, under the Fire Safety (England) Regulations 2022.
They describe the scope of the assessment, not how often it is done. Types 1 and 2 cover the common parts, types 3 and 4 also look inside flats, and types 2 and 4 include sampling that opens up the construction.